Electrical Wire Gauge & Voltage Drop Calculator
Calculate single-phase, three-phase, or DC circuit voltage drop from conductor resistance and compare against conservative reference ampacity.
- Verified Mathematical Formula
- Downloadable PDF Estimate
- Metric & Imperial Units
Electrical Wire Gauge & Voltage Drop Calculator
Calculate single-phase, three-phase, or DC circuit voltage drop from conductor resistance and compare against conservative reference ampacity.
Electrical Wire Gauge & Voltage Drop Calculator Interactive Calculator & Breakdown
2.42 %
5.81 V drop (234.19 V at load) • Preliminary table match: 10 AWG (copper) — Verify with licensed electrician
- ⚠️ Verify with licensed electrician: This calculator uses reference 75°C DC conductor resistance and does NOT evaluate ambient temperature derating, conduit fill, continuous-load 125% rules, or terminal temperature limits.
| Item / Metric | Calculated Value |
|---|---|
| Circuit Voltage Drop | 5.81 V |
| Percentage Voltage DropPreliminary table match: 10 AWG (copper) — Verify with licensed electrician | 2.42 % |
| Remaining Voltage at Load | 234.19 V |
| Reference Baseline Ampacity (10 AWG) | 30 A |
| Cost Component | Share | Amount |
|---|---|---|
| Conductor Wire Material (10 AWG copper, 1-way + 5% slack)105 ft × $1.45 | 100% | $152.25 |
| Total Preliminary Estimate | $152.25 | |
Active Calculation Steps & Disclosed Assumptions
Formula v1.0.0Live Formula Evaluation:
- • One-way length = 100 ft; Resistance = 1.21 Ω / 1,000 ft
- • V_drop = 2 × (100 / 1000) × 24 A × 1.21 = 5.81 V (2.42%)
Assumptions Applied:
- Uses 2 × OneWayLength × Amps × (1.21 Ω / 1,000 ft).
- Reference resistance from NEC Chapter 9 Table 8 uncoated conductor values at 75°C.
- Conductor cost uses your rate per 1-way unit length (for 2- or 3-conductor cable, enter cable cost per length).
Single-Phase / DC and Three-Phase Conductor Voltage Drop
For Single-Phase AC or DC: V_drop = 2 × OneWayLength × Current(A) × ResistancePerUnitLength. For Three-Phase AC: V_drop = √3 × OneWayLength × Current(A) × ResistancePerUnitLength. Voltage Drop % = (V_drop / SourceVoltage) × 100. A preliminary gauge reference must meet both the reference ampacity table and the target drop percentage; otherwise the calculator outputs "Verify with licensed electrician".
Worked Example: 100 ft One-Way Run Carrying 24 Amps at 240V Single-Phase on 10 AWG Copper
10 AWG Copper has reference resistance of ~1.21 Ω per 1,000 ft (0.00121 Ω/ft).
Sample Inputs
- Voltage: 240V (Single-Phase)
- Current: 24 A
- One-Way Length: 100 ft
- Conductor: 10 AWG Copper
Calculation Steps
- V_drop = 2 × 100 ft × 24 A × 0.00121 Ω/ft = 5.81 V
- Drop % = (5.81 / 240) × 100 = 2.42% (Within 3% branch-circuit target)
Example Result: 5.81 V drop (2.42% drop; 234.19 V at load) — Verify final sizing with a licensed electrician.
Support
Frequently Asked Questions
Quick answers about how this works, what it assumes, and where its limits are.
Why does the calculator require verification by a licensed electrician even when voltage drop is under 3%?
Conductor sizing in real installations depends on termination temperature ratings (60°C vs 75°C), continuous load multipliers (125%), ambient temperature derating, number of current-carrying conductors in a raceway, and equipment grounding requirements.
Why is one-way length multiplied by 2 for single-phase and DC circuits?
Current must travel out to the load on the ungrounded conductor and return to the source on the grounded/return conductor, doubling the total conductor path length.
Keep going
Related tools, calculators & guides
PDF Merger
Combine multiple PDF documents in custom order with optional per-file page ranges while preserving crisp vector text.
PDF Compressor
Shrink heavy PDF documents using lossless vector stream rebuilding or configurable DPI and JPEG quality re-compression.
QR Code Generator (SVG & PNG)
Create permanent, tracking-free QR codes for URLs, Wi-Fi, or text with PNG & SVG export.

Electrical Panel Upgrade Estimator
Estimate preliminary connected electrical load in amps and itemize panel upgrade material, labor, and permit costs.

AC Tonnage & BTU Calculator
Estimate preliminary cooling capacity in BTU/h and nominal refrigeration tons with climate, ceiling, sun, and insulation adjustments.

Unit Converter
Convert length, area, volume, weight/mass, and temperature across metric and imperial units.
Electrical Voltage Drop, Ohm's Law & Preliminary Wire Gauge Sizing Explained
See how conductor resistance, one-way circuit length, and single-phase vs. three-phase geometry drive voltage drop—and why licensed electrician sign-off remains mandatory.