HVAC & Electrical • Reviewed 2026-11-01Private & Local

Electrical Wire Gauge & Voltage Drop Calculator

Calculate single-phase, three-phase, or DC circuit voltage drop from conductor resistance and compare against conservative reference ampacity.

  • Verified Mathematical Formula
  • Downloadable PDF Estimate
  • Metric & Imperial Units
Audience & Scope: Mathematical voltage-drop check using standard uncoated DC resistance at 75°C. Does NOT compute conduit fill, ambient temperature derating, bundling, or continuous-load breaker rules. Verify all conductor sizing with a licensed electrician.

Electrical Wire Gauge & Voltage Drop Calculator Interactive Calculator & Breakdown

Voltage Drop on 10 AWG (copper)
2.42 %
Full Breakdown ↓
Circuit Parameters & Conductor Selection
V
A
ft
%
Voltage Drop on 10 AWG (copper)Preliminary Estimate

2.42 %

5.81 V drop (234.19 V at load) • Preliminary table match: 10 AWG (copper) — Verify with licensed electrician

  • ⚠️ Verify with licensed electrician: This calculator uses reference 75°C DC conductor resistance and does NOT evaluate ambient temperature derating, conduit fill, continuous-load 125% rules, or terminal temperature limits.
Quantity & Material Breakdown
Item / MetricCalculated Value
Circuit Voltage Drop5.81 V
Percentage Voltage DropPreliminary table match: 10 AWG (copper) — Verify with licensed electrician2.42 %
Remaining Voltage at Load234.19 V
Reference Baseline Ampacity (10 AWG)30 A
Cost Composition Share100% Budget Allocation
Materials (100%)
Itemized Cost Estimate (USD — User-Supplied Rates)
Cost ComponentShareAmount
Conductor Wire Material (10 AWG copper, 1-way + 5% slack)105 ft × $1.45100%$152.25
Total Preliminary Estimate$152.25

Active Calculation Steps & Disclosed Assumptions

Formula v1.0.0

Live Formula Evaluation:

  • • One-way length = 100 ft; Resistance = 1.21 Ω / 1,000 ft
  • • V_drop = 2 × (100 / 1000) × 24 A × 1.21 = 5.81 V (2.42%)

Assumptions Applied:

  • Uses 2 × OneWayLength × Amps × (1.21 Ω / 1,000 ft).
  • Reference resistance from NEC Chapter 9 Table 8 uncoated conductor values at 75°C.
  • Conductor cost uses your rate per 1-way unit length (for 2- or 3-conductor cable, enter cable cost per length).

Single-Phase / DC and Three-Phase Conductor Voltage Drop

For Single-Phase AC or DC: V_drop = 2 × OneWayLength × Current(A) × ResistancePerUnitLength. For Three-Phase AC: V_drop = √3 × OneWayLength × Current(A) × ResistancePerUnitLength. Voltage Drop % = (V_drop / SourceVoltage) × 100. A preliminary gauge reference must meet both the reference ampacity table and the target drop percentage; otherwise the calculator outputs "Verify with licensed electrician".

Reference Standard & Basis: NEC Chapter 9 Table 8 reference DC resistance values at 75°C and conservative 60°C/75°C baseline reference ampacity.

Worked Example: 100 ft One-Way Run Carrying 24 Amps at 240V Single-Phase on 10 AWG Copper

10 AWG Copper has reference resistance of ~1.21 Ω per 1,000 ft (0.00121 Ω/ft).

Sample Inputs

  • Voltage: 240V (Single-Phase)
  • Current: 24 A
  • One-Way Length: 100 ft
  • Conductor: 10 AWG Copper

Calculation Steps

  1. V_drop = 2 × 100 ft × 24 A × 0.00121 Ω/ft = 5.81 V
  2. Drop % = (5.81 / 240) × 100 = 2.42% (Within 3% branch-circuit target)

Example Result: 5.81 V drop (2.42% drop; 234.19 V at load) — Verify final sizing with a licensed electrician.

Support

Frequently Asked Questions

Quick answers about how this works, what it assumes, and where its limits are.

Why does the calculator require verification by a licensed electrician even when voltage drop is under 3%?

Conductor sizing in real installations depends on termination temperature ratings (60°C vs 75°C), continuous load multipliers (125%), ambient temperature derating, number of current-carrying conductors in a raceway, and equipment grounding requirements.

Why is one-way length multiplied by 2 for single-phase and DC circuits?

Current must travel out to the load on the ungrounded conductor and return to the source on the grounded/return conductor, doubling the total conductor path length.